Welcome, Guest: Register On Nairaland / LOGIN! / Trending / Recent / NewStats: 3,198,042 members, 7,966,836 topics. Date: Saturday, 05 October 2024 at 03:07 AM |
Nairaland Forum / Ayoade333's Profile / Ayoade333's Posts
(1) (2) (3) (4) (5) (6) (7) (8) (of 8 pages)
Nairaland / General / Re: I Need A Website Developer by Ayoade333: 8:54am On Oct 14, 2020 |
I also need delivery website if the cost is not much ooooo...... |
Nairaland / General / WE BUILD SCHOOL SOFTWARE, HOTELS ,BIG E-COMMERCE, PAYMENT INTEGRATION ETC... by Ayoade333: 5:09pm On Sep 25, 2020 |
We are software developer, we build deferent kind of software,, SCHOOL SOFTWARE, HOTEL BOOKING SOFTWARE,BIG E-COMMERCE SOFTWARE, FINANCIAL SOFTWARE, BANKING SOFTWARE , RESTAURANT SOFTWARE... Thinking about setting up an online payment form for your business? To accomplish this task you may be deciding between third-party solutions or developing your own in-house solution. Each option has its own set of pros, cons, and costs that you’ll want to consider as you determine the right solution. Here’s what you need to know about choosing the best option for your business, setting up an online payment form, and then optimizing the form to make it as easy as possible for your customers to use. call 08037110658 1 Share
|
Business / Re: Technicality In Blast Cold Room Building And Unit Installation by Ayoade333: 4:50pm On Jul 24, 2020 |
You are welcome ,,,we base in Lagos...... |
Nairaland / General / Re: Cold Room Property With Land by Ayoade333: 8:20pm On Jul 22, 2020 |
Thank God another project completed in Ogun state...contact us @ kol-lek1 Nig Ltd 08037110658 1 Share
|
Business / Re: Technicality In Blast Cold Room Building And Unit Installation by Ayoade333: 8:18pm On Jul 22, 2020 |
Thank God another project completed in Ogun state...contact us @ kol-lek1 Nig Ltd 08037110658 1 Share
|
Nairaland / General / Re: Freezer & Cold Rooms Construction by Ayoade333: 8:16pm On Jul 22, 2020 |
Thank God another project completed in Ogun state...contact us @ kol-lek1 Nig Ltd 08037110658 1 Share
|
Nairaland / General / Re: Freezer & Cold Rooms Construction by Ayoade333: 8:11pm On Jul 22, 2020 |
@Life najeje am sorry for my late response.... I work late on the project this days.....concerns your freezer its... According to your complain.... The freezer as internal leakages within the pipe.... This is the solution...u can give it to engineer to run another pipe inside the freezer and couple it back or get another freezer... Thanks |
Business / Re: Cold Room Building And Installation by Ayoade333: 8:04pm On Jul 21, 2020 |
Another project it's on it way....... |
Business / Re: Technicality In Blast Cold Room And Unit Installation by Ayoade333: 8:02pm On Jul 21, 2020 |
another project it's on the way...... wash out...... |
Food / Re: Teach Me About Shawarma Business by Ayoade333: 8:00pm On Jul 21, 2020 |
You ask questions about ur freezer.... the freezer has internal leakage..... You need to run another pipe internally to make the freezer comes quality..... |
Nairaland / General / Re: Trade Nigeria Thumps Up To Fg's Support For Dr. Okonjo-iweala's Ambition by Ayoade333: 3:03pm On Jul 17, 2020 |
TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835 |
Politics / Re: ‘NDDC Spent N82bn On Condolences, DTA, COVID-19, Others In 5 Months’ by Ayoade333: 2:59pm On Jul 17, 2020 |
TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835 |
Politics / Re: Buhari Receives Nigeria’s First Artisanally-Mined Gold by Ayoade333: 2:57pm On Jul 17, 2020 |
TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835 |
Politics / Re: Joy Nunieh Testifies Before House Of Representatives Committee by Ayoade333: 2:55pm On Jul 17, 2020 |
TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835 |
Politics / Re: Arthur Eze, Elumelu, Obi, Ikwechegh Make List Of Top Influential Igbo People by Ayoade333: 2:53pm On Jul 17, 2020 |
TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835 |
Politics / Re: Nairaland Says No To Secessionists by Ayoade333: 2:49pm On Jul 17, 2020 |
TECHNICALITY IN BUILDING AND INSTALLATION OF COLD ROOM, NEVER GIVE A COLD ROOM PROJECT TO A QUAKE ENGINEERS 1, COLD ROOM equipment compressor unit assembling and installation-we are professional fabricated compressor rack factory over 10 years. 2, COLD ROOM equipment evaporators installation When selecting the hanging point position, firstly consider the best position for the air circulation, and then consider the direction of the cold storage structure. The space between the evaporator and the cold room panel should be bigger than the thickness of the evaporator. All the hangers of the evaporator should be fastened, and the bolts and hanging bolts should be closed with a sealant to prevent air leakage. When the evaporator is too heavy, using a 4 or 5 angle iron to make the beam. The beam should span to another roof and wall panel to reduce the weight. 3, Refrigeration equipment piping installation technology The diameter of copper pipe should strictly match with the interface diameter of compressor suction and exhaust valve. When the condenser and compressor are separated more than 3 meters, the pipe diameter should be increased. Keep the distance between the condenser suction air side and the wall over 400mm, and keep the distance between the outlet and the obstacle more than 3 meters. Discharge pipe and return pipe should have a certain slope. When the condenser position is higher than the compressor, the discharge pipe should be sloped to the condenser and a liquid ring should be installed at the compressor discharge mouth to prevent the gas cooling to liquid and returning to the mouth after compressor off. The U-bend should be installed at the exit of the evaporator air return pipe. The air return pipe should be sloped toward the compressor to ensure oil return smoothly. The expansion valve should be installed as close as possible to the evaporator. The solenoid valve should be installed horizontally. The valve body should be vertical and we should notice the direction of the liquid. after the completion of the welding of the entire refrigeration system, to do airtight experiments, high-pressure side of nitrogen filling 1.8MP. The low-pressure side is filled with nitrogen 1.2MP. During filling, soapy water is used for leak detection. Carefully check the welding, flange and valve. The pressure is kept for 24 hours. 4, Electrical system installation The selection of wire must have a safety factor. The temperature of the wire surface must not exceed 4 degrees during the compressor unit operating or evaporator defrosting . 5, Whole refrigeration equipment system commissioning Check all valves in the refrigeration system if it is in the normal open state or not, especially the exhaust stop valve. Do not close it. Open the cooling water valve of the condenser. If it is an air-cooled condenser, turn on the fans. Check that if the amount of water and the air flow rate meet the requirements or not. the electrical control circuit should be tested separately in advance, we should pay attention to whether the power supply voltage is normal before starting. Whether the oil surface of the compressor crankcase is in the normal position or not, it should generally be maintained at the horizontal centerline of the oil monitor. Why choose us? Your Cold Room Expert....KOL-LEK1 NIG LTD ..CONTACT US 08037110658 OR WHATAP US @ 08188892835 |
Politics / Re: Ijaw, Itsekiri Unite Against Oil Companies, 20 Years After Warri War by Ayoade333: 2:58am On Jul 15, 2020 |
New cold room project began in ....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 we build and install cold room nation wide..... 1 Share
|
Politics / Re: Senators Bicker Over Innoson Motors Boss, Chukwuma by Ayoade333: 2:55am On Jul 15, 2020 |
New cold room project began in ....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 we build and install cold room nation wide..... 1 Share
|
Politics / Re: Akpabio: Nothing Must Happen To Joy Nunieh - Wike by Ayoade333: 2:53am On Jul 15, 2020 |
New cold room project began in ....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 we build and install cold room nation wide..... 1 Share
|
Politics / Re: Buhari Backs Keyamo On 774,000 Jobs by Ayoade333: 2:50am On Jul 15, 2020 |
New cold room project began in ....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 we build and install cold room nation wide..... 1 Share
|
Politics / Re: Major Shake-up As 37 Nigerian Army Generals Redeployed by Ayoade333: 2:46am On Jul 15, 2020 |
New cold room project began ...contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 1 Share
|
Politics / Re: Edo 2020: Ize-iyamu Won’t Get Up To 30 Percent Votes – Crusoe Osagie by Ayoade333: 2:45am On Jul 15, 2020 |
New cold room project began ....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 1 Share
|
Politics / Re: Nairaland Says No To Secessionists by Ayoade333: 2:42am On Jul 15, 2020 |
New cold room project began in Ogun state....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 1 Share
|
Business / Re: Technicality In Blast Cold Room Building And Unit Installation by Ayoade333: 2:35am On Jul 15, 2020 |
New cold room project began in Ogun state....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08037110658 1 Share
|
Business / Re: Technicality In Blast Cold Room And Unit Installation by Ayoade333: 2:33am On Jul 15, 2020 |
New cold room project began in Ogun state....contact KOL-LEK1 NIG LTD @ 08037110658 OR WHAT WHAT US @ 08188892835 1 Share
|
Business / Re: Technicality In Blast Cold Room And Unit Installation by Ayoade333: 1:37pm On Jul 14, 2020 |
Project continued 1 Share
|
(1) (2) (3) (4) (5) (6) (7) (8) (of 8 pages)
(Go Up)
Sections: politics (1) business autos (1) jobs (1) career education (1) romance computers phones travel sports fashion health religion celebs tv-movies music-radio literature webmasters programming techmarket Links: (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Nairaland - Copyright © 2005 - 2024 Oluwaseun Osewa. All rights reserved. See How To Advertise. 52 |