Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 8:18pm On Apr 06, 2018 |
Lolz! I was with a client recently who proudly demonstrated same for the GoodWe inverter - he disconnected the battery leaving PV on at full power at midday - the inverter threw an error, disconnected the PV and shut down safely. This is one up for the Victron and GoodWe folks. Interestingly, it is not that MorningStar blows up anytime you disconnect battery with PV on - there is a power clamp limit that it can safely clamp - I have disconnected battery with incoming 2000w PV and the MorningStar took the hit and continued working - this on a test CC that I salvaged of course The CC I blew had a 4.5kw array putting out 3.2kw (MorningStar was current limiting) when the battery MCB tripped and released the magic smoke - the newest firmware have updated the internal workings to better use the electronic protections in the MorningStar. For EPever, they can clamp between 1.1 and 1.5times max rated current I believe. I will write to MorningStar as well to clarify the clamp current limits and exactly how much improvement the new firmware updates have made. pranil: |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 8:25pm On Apr 06, 2018 |
Many thanks for your very clear answers Oga Chris. It appears Europe is very anal about regulations for chemical substances coming in and out of the Eurozone and HazMat classifications - I am privy to several incidents where we paid heavily to obtain permits to bring in chemicals and catalysts used for refinery operations and now sending back the HazMat spent chemicals for safe disposal in an Eurozone based landfill is proving to be a total nightmare. [quote author=chris81964 post=66488595][/quote] 1 Like |
Re: Solar Energy, A Complement To FTA by davodyguy: 9:30pm On Apr 06, 2018 |
Chief niyi, wanna ask a question. When I was using 1000w 12v inverter with 540watts Panels via 40A CC on my 2*200AH batteries connected in parallel, the CC drops about 30A on the 400Ah batteries. Now I'm using 2000watts 24v inverter same 540watts Panels via 40A CC on my 2*200AH batteries connected in series, the CC drops about 14A on the 400Ah batteries.My question is doe the CC adjust based on the battery connection or voltage? |
Re: Solar Energy, A Complement To FTA by makavele: 9:58pm On Apr 06, 2018 |
pranil: my ePever has in truth faced a battery line trip and didn't fail. It took me about 15 minutes before I found out . . the CC shut itself down and rebooted nicely upon connection |
Re: Solar Energy, A Complement To FTA by makavele: 10:02pm On Apr 06, 2018 |
davodyguy: Less volts = more amps; and vice versa . . since you increased voltage to 24V; battery would now be seeing half the amps under the same conditions CC adjusts based on voltage 2 Likes |
Re: Solar Energy, A Complement To FTA by davodyguy: 10:07pm On Apr 06, 2018 |
makavele: Thanks Chief I hope its true lol |
Re: Solar Energy, A Complement To FTA by makavele: 10:16pm On Apr 06, 2018 |
2 Likes |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 5:11am On Apr 07, 2018 |
Oga Makavele is on point. Its the same CC and same panels and the power output in both 12v and 24v configurations is roughly the same. Power = Amps × Volts So if we assume your batteries charged at a reference 14.4volts in your 12v parallel setup and 28.8volts in your 24v series setup (14.4 × 2 [12v batteries in series]) Then at 12v nominal, Panel/CC power output was 30Amps × 14.4volts = 432watts. At 24v nominal, Panel/CC power output is 14Amps × 28.8volts = 403watts. So you see that the Panel/CC power output is almost the same - differences may be due to change of charging profile, ambient weather at the time you checked e.t.c davodyguy: makavele: |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 5:44am On Apr 07, 2018 |
makavele: Over sabi dey worry u(I can't blame u though; it's a DIY thread where anybody can answer ur question), he specifically mentioned Niyi, u see ur name and others there? 3 Likes |
Re: Solar Energy, A Complement To FTA by davodyguy: 7:23am On Apr 07, 2018 |
NiyiOmoIyunade:Thanks bro |
Re: Solar Energy, A Complement To FTA by davodyguy: 7:26am On Apr 07, 2018 |
Oshomo12:Haha. Chief Makavele has/had always been helpful too. Trust me, I respect all contributions and I stayed in my last post, that when you don't know the way, you must ask for direction. That's my policy in life. Tomorrow, I can even ask you for guidance |
Re: Solar Energy, A Complement To FTA by DMerciful(m): 10:21am On Apr 07, 2018 |
Flow batteries (fuel cells) are like ur internal combustion engines that uses the chemical energy of a fuel to thermally produce mechanic energy by the controlled combustion of the fuel in a closed chamber but only that fuel cells convert chemical energy directly to electrical energy making them more efficient and with a potential of 80% efficiency however material is still consumed. Though a solar system can be incorporated to electrolyse water into hydrogen that can be stored and used but the initial investment is high. Lithium on the other hand makes energy harness and storage easier. I consider these systems as perpetual motion machine of probably the 4th kind pranil: |
Re: Solar Energy, A Complement To FTA by davodyguy: 1:22pm On Apr 07, 2018 |
Just completed a DIY. Now 4 panels in series and parallel connection. 270watts *2 (Series) 270watts +250 watts (Series) Then paralleled the two series' Total wattage now 1040w from Panels PV= 68v Amps dropping on batteries now 30.1A 200Ah *2 in series 2kva Prag Pure sine wave Thanks DMerciful pranil NiyiOmoIyunade Makavele Missed out some names. Please not deliberate. It's the phone. |
Re: Solar Energy, A Complement To FTA by DMerciful(m): 2:50pm On Apr 07, 2018 |
Congratulations.... Upgrading is always sweet when the output is as expected. Solar as a way of energy independence is the way to go davodyguy: |
Re: Solar Energy, A Complement To FTA by Monlo(m): 4:14pm On Apr 07, 2018 |
davodyguy: Enjoy,there is nothing that is as sweet as Free energy from the sun(RE) cum FTA. One love. 1 Like |
Re: Solar Energy, A Complement To FTA by makavele: 6:01pm On Apr 07, 2018 |
Oshomo12: Niyi; shey make I reply this guy; or make i free am ? 2 Likes |
Re: Solar Energy, A Complement To FTA by zeestone99(m): 6:40pm On Apr 07, 2018 |
makavele:No involve niyi, jst block am 4 junction... 2 Likes |
Re: Solar Energy, A Complement To FTA by sinistrian(m): 8:54pm On Apr 07, 2018 |
I am concerned about what happens when the inverter feeds incoming mains (or generator power) directly to house appliances when it's in bypass mode. The other day my gen produced almost 290V and blew up the charging circuitry of my DC fans. Another time the voltage from PHCN was so low (it got as bad as 130VAC) the LED lights were barely providing any visibility, yet the inverter refused to take over. In both cases it just just fed the out-of-range voltage straight to house devices. I would like the inverter to only feed regulated power to appliances. Pranil mentioned the AVS30 but it seems to only work with a range of 'acceptable' voltages - it doesn't step up/down and will just cut off if dirty power comes in. Would a 5kva relay-stabilizer (non-servo because i'm cutting costs and also because I don't mind the +/- 10% variation in output voltage) be appropriate to put in between mains power and a 3kva inverter proper? |
Re: Solar Energy, A Complement To FTA by makavele: 10:19pm On Apr 07, 2018 |
zeestone99: You garrit but make we forgive the hood rat. How your side? 1 Like |
Re: Solar Energy, A Complement To FTA by duwdu: 10:26pm On Apr 07, 2018 |
davodyguy: Congrats, davodyguy. But please permit me, guys... isn't the total watts from the panels in this configuration not supposed to be limited to 270 + 250 = 520 Watts? Or, have I been missing/muddling up some of my lessons learnt? (Honestly, I'm relatively new to all of this.) ........ P34c3 ..... ... |
Re: Solar Energy, A Complement To FTA by duwdu: 10:27pm On Apr 07, 2018 |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 10:52pm On Apr 07, 2018 |
makavele: What I 'do'? Note: it's like u didn't get my point. |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 10:56pm On Apr 07, 2018 |
zeestone99: Correct! By d way, did u grow up around Mushin(just asking)? |
Re: Solar Energy, A Complement To FTA by makavele: 11:05pm On Apr 07, 2018 |
duwdu: That's what happens when you use mismatched panels ... 250 + 350 will not give 600 because the 350 panel will be dragged down and behave like the 250 one so you'll be getting circa 500 instead. Naaa.. i was just kidding ooo |
Re: Solar Energy, A Complement To FTA by makavele: 11:07pm On Apr 07, 2018 |
Oshomo12: What you do? Askorr .... Ibeere!! you know the rest |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 11:09pm On Apr 07, 2018 |
Pranil mentioned the AVS30 but it seems to only work with a range of 'acceptable' voltages - it doesn't step up/down and will just cut off if dirty power comes in. Would a 5kva relay-stabilizer (non-servo because i'm cutting costs and also because I don't mind the +/- 10% variation in output voltage) be appropriate to put in between mains power and a 3kva inverter proper? [/quote] You need a stab after the mains, i.e. Ur inverter connects to a stab. Otherwise, garbage in, garbage out! |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 11:14pm On Apr 07, 2018 |
Re: Solar Energy, A Complement To FTA by Dam5reey(m): 2:00am On Apr 08, 2018 |
makavele: Okay.. It actually depends the VOC, ISC and connection (either series or parallel) If your VOC is the same 350+250 will give you up to 580 I do get 200+ from 140 + 80 and not 160 |
Re: Solar Energy, A Complement To FTA by makavele: 4:50am On Apr 08, 2018 |
Dam5reey:
|
Re: Solar Energy, A Complement To FTA by zeestone99(m): 9:03am On Apr 08, 2018 |
Oshomo12: Dnt mind me, jst being sarcastic... Im a pastor... Peace be with you and happy Sunday |
Re: Solar Energy, A Complement To FTA by zeestone99(m): 9:49am On Apr 08, 2018 |
makavele:I'm good man, hapi Sunday |
Re: Solar Energy, A Complement To FTA by zeestone99(m): 9:51am On Apr 08, 2018 |
makavele: Yeah u right, one of d problems of mismatching panels |
(1) (2) (3) ... (381) (382) (383) (384) (385) (386) (387) ... (1853) (Reply)
FTA Live Football Matches Announcement Thread / Free To Air Satellite Tv General Thread
Viewing this topic: staticstring and 2 guest(s)
(Go Up)
Sections: politics (1) business autos (1) jobs (1) career education (1) romance computers phones travel sports fashion health religion celebs tv-movies music-radio literature webmasters programming techmarket Links: (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Nairaland - Copyright © 2005 - 2024 Oluwaseun Osewa. All rights reserved. See How To Advertise. 53 |