Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 10:24am On Dec 06, 2018 |
Oga KieKie, Please are these pictures of one single location or two different places? I see what appears to be your trusty CyberPower 3.5kva inverter in one picture but in the other picture with the battery monitors, I see something that looks Victronish and from the size dimensions looks more like an inverter than a a CC - I could be off though because all the pics are rather darkened. Do you get any assist from the Grid or Gen overnight? It appears with your AC on overnight, you are running roughly 1.1kw on 6pcs of 12v 200Ah batteries (14.4kwh of storage) so you would both be exceeding the C20 discharge rate and most likely going below 50% DoD as well if you get no Grid or Gen assist. If you are getting no grid assist, what does your battery voltage look like in the mornings after you have run your AC overnight? kiekie1: 4 Likes |
Re: Solar Energy, A Complement To FTA by kiekie1(m): 10:45am On Dec 06, 2018 |
NiyiOmoIyunade: Yes that's a Victron 70a mppt beside the monitors and a 24hrs USA online smart inverter which triggers the refrigerator programmed timers on 24hrs basis and hasn't gone off for about 4 years counting. I am partially offgrid as our grid supply is highly epileptic! I mentioned a while ago, my die-hard cyberpower only comes on basically for opportunistic high wattage loads, I treat it like a baby because the service parts is very rare .. Yes you saw that high kw load rating because all those loads listed was ON and AC only came on when Fridge went OFF. Flood led and AC overnight reads 800-830w , only when AC compressor kicks in since am on 25-28° temp settings. When AC compressor cuts, I get roughly +/-70watts max on system display! Worst battery volt i have seen overnight is 23 / 23.5v mainly during dull weather which doest bother my bank at all, my inverters set depth of discharge is 21.5v min but I have never experienced low battery alarm nor shut down because i and my household are very practical about load management ... Note:refrigerator compulsorily works 12-6am overnight , and intermittently comes on for an hour or 2 by late evening on timer settings. Cheer's |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 11:52am On Dec 06, 2018 |
Thanks Oga KieKie, Please tell us more about the inverter bolded below. kiekie1: Also, are the timers integrated into the inverter or they are normal external devices? I would assume this inverter is low wattage or at least smaller than your CyberPower since you still prefer to use the CyberPower for your larger loads. Finally how are you able to get a split 1.5hp AC (non inverter type) to consume 800 to 830watts? Or is it a different AC in use now? kiekie1: 3 Likes |
Re: Solar Energy, A Complement To FTA by kiekie1(m): 1:10pm On Dec 06, 2018 |
NiyiOmoIyunade: Hmmn need to prepare for the above JAMB question by evening ... Am on supplies now 2 Likes |
Re: Solar Energy, A Complement To FTA by olaade21: 1:21pm On Dec 06, 2018 |
Re: Solar Energy, A Complement To FTA by CAROLYN19: 2:03pm On Dec 06, 2018 |
Call us on 08066332919 for your Industrial Power Back Up equipment
|
Re: Solar Energy, A Complement To FTA by DMerciful(m): 6:17pm On Dec 06, 2018 |
Kilode! How can you say it's similar to this? Depending on the usage conditions and your ability to test, used batteries could be a good bargain.If you know the seller, the ultimate test is to run it for a day(24hrs)then pay Oshomo12: |
Re: Solar Energy, A Complement To FTA by DMerciful(m): 7:06pm On Dec 06, 2018 |
Exaggerated performance....If you know you know 8 Likes |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 7:18pm On Dec 06, 2018 |
Seconded! The one sure way to test a battery is by a sustained load test. Under a suitably calibrated load, a battery's true capacity or lack thereof will quickly show DMerciful: |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 7:23pm On Dec 06, 2018 |
Oga Pharyn, Well done and more power to your elbow! My only request is that you teach me (in private) how to land clients like these One such job on a monthly basis should do me very well indeed! More power and more grace Sir. Pharyn: 2 Likes 1 Share |
Re: Solar Energy, A Complement To FTA by Valto(m): 7:24pm On Dec 06, 2018 |
pls does anyone have affordable 2pcs 200ah fairly used AGM battery that is still in very good condition for sale? pls contact valto2020@yahoo.com |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 7:42pm On Dec 06, 2018 |
Let it not be said that one man is trying to rain on another man's parade! But just to seek knowledge and ensure that all claims are put in their proper perspective, lest the readers be misinformed or deceived. DMerciful: |
Re: Solar Energy, A Complement To FTA by earthrealm(m): 8:02pm On Dec 06, 2018 |
Valto: yes o, i may have beta agm batts barely used 1 Like |
Re: Solar Energy, A Complement To FTA by Valto(m): 8:25pm On Dec 06, 2018 |
earthrealm:oga nawa oo. u no see me.. i jump am pass 3 Likes |
Re: Solar Energy, A Complement To FTA by DUNKA(m): 8:30pm On Dec 06, 2018 |
DMerciful:we know very well. No be today e start 3 Likes |
Re: Solar Energy, A Complement To FTA by DUNKA(m): 8:37pm On Dec 06, 2018 |
NiyiOmoIyunade:He can get away with it on the other groups that are less informed but certainly not on this group as the gurus here can easily see through any exaggerated claims I am sure you he will not respond again after you caught him out. On delivery supplies indeed Frankie can never change his devious ways 11 Likes |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 9:35pm On Dec 06, 2018 |
Most of the good options (value & premium inverters and CCs) are within the 12v to 48v range. Given that your batteries are 12v units you will find best battery balance at 12v but your maximum efficiency at 48v. Borrowing from how 12v batteries in parallel stay better in sync with each other, one may contrive a similar arrangement with multiple parallel bank 24v or 48v battery setups by creating additional parallel links between each position in each bank. I will post a diagram in a bit. This solution is not a cure all though, it solves a part of the problem but still leaves something unsolved. It has worked well for me so far vs. doing the conventional approach though. olaade21: |
Re: Solar Energy, A Complement To FTA by harveyspec: 10:10pm On Dec 06, 2018 |
good evening all, compliments of the season!! I want to make a suggestion. I propose that the markerters who spam this thread with a long list of products should create a new thread & list all products/prices & update when necessary. Then they should drop the link to that thread here. "contact us for your Solar need, for avaliable products/updated prices visit http:/......" CAROLYN19 doesn't spam, he/she leaves a short message & that's it with occasional repost. Its insulting that despite the outcry of contributors here, folks are still bent flooding the pages with adverts 12 Likes |
Re: Solar Energy, A Complement To FTA by earthrealm(m): 10:11pm On Dec 06, 2018 |
Valto: Hahahaha. Oga i see u wella.you no fit escape me I get abt 4months gently used batts and 7months batts. In fabulous condition..date of manufacture 2018. And late 2017. Y u dey fear....y u no wan patronize me naaaauu |
Re: Solar Energy, A Complement To FTA by olaade21: 10:33pm On Dec 06, 2018 |
NiyiOmoIyunade: Nice, looking forward to your post. |
Re: Solar Energy, A Complement To FTA by idsolar(m): 10:52pm On Dec 06, 2018 |
earthrealm: chai u no go kill me with laughter. 1 Like |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 12:00am On Dec 07, 2018 |
DMerciful: Lol No mind me fa! I no dey near used batteries, except the ones used by me! |
Re: Solar Energy, A Complement To FTA by Saipro(m): 7:06am On Dec 07, 2018 |
olaade21:If you're starting fresh, 48V is really good. It's the lowest current option for the typical home system. High current is the bane of electricity transmission because cable resistance is fairly constant. That leaves you with voltage to mess around with thus lowering your current. In addition, 48V will always require fewer strings if you use the same batteries (as opposed to 12v and 24V). Think about your needs. If a 48V system will work for you (including consideration for DC devices or not), please go ahead with it. |
Re: Solar Energy, A Complement To FTA by EricDManske(m): 7:07am On Dec 07, 2018 |
Locksmith Parkland focus on locksmith service and garage door repair with replacement and other maintenance services in Parkland. Call us and obtain our technicians with best expertise to figure your drawbacks of repair requirement. |
Re: Solar Energy, A Complement To FTA by Saipro(m): 7:28am On Dec 07, 2018 |
NiyiOmoIyunade:Often true but ... I have on occasion seen one bad cell in a single battery promptly spawn bad cells in parallel batteries. Case in question had a bank of 4 batteries in parallel. Things were good for a long while so I went to sleep. I didn't notice until 2 of them had irrecoverably bad cells. I went on to separate into 2 banks of 12v x 2 in dual parallel config. I believe I made a post about it on this forum. From that experience, it became pretty apparent that 12V batteries are cool but they're just 2V x 6 batteries hard-wired together in a single string The moment you run them in parallel, you experience the same issues as 2V x6/4v x 3/6V x 2 batteries in parallel without the benefit of isolating the bad cell without removing the entire battery. If you believe in God, you might need to pray your bank doesn't develop rogue cells. |
Re: Solar Energy, A Complement To FTA by Saipro(m): 7:52am On Dec 07, 2018 |
EricDManske:The Yoruba say, "a kì í j'èkuru kó tán l'ábọ́ kí ẹnìkan tún ma gbọn ọwọ́ si". 3 Likes |
Re: Solar Energy, A Complement To FTA by Oshomo12(m): 8:11am On Dec 07, 2018 |
Saipro: The best config then is 2v(a cell) in series to form a battery. Thereafter continue with parallel and not exceeded 3strings. Batteries and their wahala. |
Re: Solar Energy, A Complement To FTA by kiekie1(m): 8:43am On Dec 07, 2018 |
Call us now! 081-350-319-51.. Long batteries 200a ..... 120k We always encourage our customers to start from a point , its a gradual process if budget is an issue! Kindly view & like our video below and pardon the video quality . https://www.youtube.com/watch?v=CNQuDoHxtis
|
Re: Solar Energy, A Complement To FTA by AidanGDunbar: 12:24pm On Dec 07, 2018 |
Orting Locksmith offers optimal locksmith and garage door repair solutions by trained technicians to assist you better standard. Call now and receive same day repair service. We fix all your requirement on the day you ask. |
Re: Solar Energy, A Complement To FTA by S007: 1:09pm On Dec 07, 2018 |
AidanGDunbar: I hope this person can see. U better wake up from ur sleep, carry your locks and get out of our thread. |
Re: Solar Energy, A Complement To FTA by surrogatesng: 5:21pm On Dec 07, 2018 |
Brand new 75ah deep cycle battery for sale.Call 08170368264
|
(1) (2) (3) ... (479) (480) (481) (482) (483) (484) (485) ... (1855) (Reply)
FTA Live Football Matches Announcement Thread / Free To Air Satellite Tv General Thread
Viewing this topic: 4 guest(s)
(Go Up)
Sections: politics (1) business autos (1) jobs (1) career education (1) romance computers phones travel sports fashion health religion celebs tv-movies music-radio literature webmasters programming techmarket Links: (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Nairaland - Copyright © 2005 - 2024 Oluwaseun Osewa. All rights reserved. See How To Advertise. 66 |