Re: Solar Energy, A Complement To FTA by DUNKA(m): 10:14am On Feb 03, 2020 |
ojeysky:please what capacity of lithium batteries will replace eight ( ![]() |
Re: Solar Energy, A Complement To FTA by simydan(m): 11:29am On Feb 03, 2020 |
DUNKA: I guess your 8×200ah batteries are configured in 4S 2P at 48V 400AH. If that's correct your lithium ion configuration will be 2units of 48V 200AH to be connected in parallel. But in real sense, since Lithium battery capacity can double lead acid battery capacity you can do a unit of 48V 200AH ~ 10KW. You can contact me for a good deal! 1 Like |
Re: Solar Energy, A Complement To FTA by BRIGHTSOLAR(m): 11:40am On Feb 03, 2020 |
ONLINE DELIVERY OF RENEWABLE ENERGY MATERIALS INVERTER MICROTECH INVERTER 900VA,12V N46,000 1.1KVA,12V N53,000 1.6KVA/24V N72,000 2.3KVA/24V N90,000 2.6KVA/36V N105,000 3.6KVA/48V N170,000 5.2KVA/48V N340,000. 5.5KVA/96V N340,000 10KVA/180V N790,000 KARTEL INVERTER WALL MOUNTED SERIES 1.5kva/12v- N60,000 2kva/12v- N85,000 2kva/24v- N85,000 2.5kva/12v- N95,000 2.5kva/24v- N95,000 3.5kva/24v – N115,000 5kva/24v- N150,000 5kva/48v – N155,000 GENEXTECH SERIES 2KVA/24V(600W MPPT) #138,000 3KVA/24V(600W MPPT) #149,000 3KVA/24V(1500W MPPT) #194,000 3KVA/48V(3000W MPPT) #202,000 5KVA/48V(3000W MPPT) #306,000 10KW/48V(14850W MPPT) #1,660,000 BATTERY LUMINIOUS BATTERY 12V/200AH N 125,000 ELSON BATTERY 12V/200AH N 115,000 M POWER BATTERY 12V/200AH N 105,000 EASTMAN 12V/200AH TALL TUBULAR BATTERY N95,000 LUMINIOUS 12V/220AH TALL TUBULAR BATTERY N95,000 GLT BATTERY 12V/200AH N 90,000 ZEEDIX BATTERY 12V/200AH N 95,000 RITAR BATTERY 12V/200AH N 130,000 GENUS BATTERY 12V/200AH N125,000 QUANTA BATTERY 12V/200AH N 120,000 EZOR BATTERY 12V/200AH N 100,000 BATTERY RACK BATTERY RACK 2 BATTERY N 15,000 BATTERY RACK 4 BATTERIES N 30,000 BATTERY RACK 8 BATTERIES N 50,000 CHARGE CONTROLLER SRNE MPPT 12/24/36/48V/60A N90,000 FANGUNPSUN MPPT SERIES 60A 48v N120,000 80A 48v N150,000 SOLAR PANELS TRINA SOLAR PANEL 300w MONO -N85,000 350w MONO -N110,000 JINKO SOLAR PANEL JINKO SOLAR 370WATT MONO - N80,000 JINKO SOLAR 340WATT MONO - N70,000 JINKO SOLAR 280WATT MONO - N57,000 JINKO SOLAR 265WATT POLY - N55,000 ERA SOLAR PANEL ERA SOLAR 300WATT MONO – N50,000 ERASOLAR 400WATT MONO – N56,000 CANADIAN SOLAR PANEL MONO- 300w. N55,000 (BULK PURCHASE ONLY) 305w. N57,000 (BULK PURCHASE ONLY) ACCESSORIES PROGRAMMABLE Digital timer 15A N7,000 PROGRAMMABLE Digital timer 25A N9,000 BATTERY VOLTMETER INDICATOR ------------------#1,700 INSTALLATION KITS L.FOOT N1,000 (MINIMUM ORDER 10 PIECES) MID CLAMP N1,000 (MINIMUM ORDER 10 PIECES) END CLAMP N1,000 (MINIMUM ORDER 10 PIECES) Call-07058562938 Bright Energy WHATSSAP 08187995847 FOR PURCHASE/ DELIVERY /INSTALLATION NATIONWIDE visit our website www.brightsenergy.com |
Re: Solar Energy, A Complement To FTA by idsolar(m): 5:41pm On Feb 03, 2020 |
guys pls this luminous hybrid inverter battery selector if you are using flooded battery and the selection points on inverter are: 1. Tubular 2. flat plate 3. Gel/VRLA where will set flooded battery? the i,.Chg point is it suppose to be on or off? thanks |
Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 7:08pm On Feb 03, 2020 |
Set to 'TUBULAR' if your battery is flooded. I think the Luminous maxes out at 14.4v charge voltage though. Most flooded batteries prefer a high voltage charge and may die early if they are not absorbed and equalized at a sufficiently high voltage. idsolar: 1 Like |
Re: Solar Energy, A Complement To FTA by Barezzi(m): 8:18pm On Feb 03, 2020 |
So no hope for folks like me with average loads in the KW range ![]() simydan: |
Re: Solar Energy, A Complement To FTA by simydan(m): 8:53pm On Feb 03, 2020 |
Barezzi: There's hope for you sir! ![]() You just need a budget, then work with it and if cash flow get as e be, then you chill for a while and plan ahead... Hoping to have you amongst the LFP family soon Sir. |
Re: Solar Energy, A Complement To FTA by ojeysky(m): 9:26pm On Feb 03, 2020 |
DUNKA: The way I understand it 12v 200AH lead acid = 12v 200AH lithium. The difference comes in the depth of discharge..... while you can use lithium entirely without issues, doing so with lead acid will kill it faster. So if we work with 50% DOD as safe depth for lead acid then the equivalent for lithium will be 24V 200AH X 2 12V 200AH X 4 48V 200AH Gurus in the house may know better though ![]() |
Re: Solar Energy, A Complement To FTA by ojeysky(m): 9:27pm On Feb 03, 2020 |
4 Likes |
Re: Solar Energy, A Complement To FTA by Barezzi(m): 9:33pm On Feb 03, 2020 |
@Ojeysky, look ya post and run through ya numbers again. The thing no jive at all... |
Re: Solar Energy, A Complement To FTA by ICraft(m): 1:12am On Feb 04, 2020 |
the truth is that most people don't obey the 50% DOD rule for Lead Acid Batteries, a good number of Inverters in the market shut down at 40v for 48v models, which is 10 volt for a 12 v model, this is already way below the 50% DOD target for battery longevity. My point is that its not practical to believe that you need only half your lead acid battery capacity if you are switching over to any Lithium Chemistry. I used 24 pieces of Agisson 2v 500AH (48v 500AH) from 2011 to December 2016 when I switched over to Lithium. for those slightly over 5 years, my battery bank never got below 47.4v. I sold the batteries to a friend who just retired them last December and embraced Lithium also. Lead acid batteries can last a long time if well managed. 6 Likes |
Re: Solar Energy, A Complement To FTA by idsolar(m): 5:30am On Feb 04, 2020 |
[quote author=NiyiOmoIyunade post=86349913]Set to 'TUBULAR' if your battery is flooded. I think the Luminous maxes out at 14.4v charge voltage though. Most flooded batteries prefer a high voltage charge and may die early if they are not absorbed and equalized at a sufficiently high voltage. [/quote Nagode. |
Re: Solar Energy, A Complement To FTA by abbeyforex(m): 5:55am On Feb 04, 2020 |
Thanks so much, I have informed the installer but he kept telling me different stories and arguing that the battery is good unicmarket: |
Re: Solar Energy, A Complement To FTA by abbeyforex(m): 5:56am On Feb 04, 2020 |
Okay sir ICraft: |
Re: Solar Energy, A Complement To FTA by abbeyforex(m): 5:59am On Feb 04, 2020 |
It is only the freezer that I have on the inverter and 1piece 15W led bulb mank1234: |
Re: Solar Energy, A Complement To FTA by simydan(m): 7:14am On Feb 04, 2020 |
ICraft: I totally agree with you sir! Even a grade B battery can last a bit longer if properly managed. But the problem seem to be with squeezing out more than what a back up is designed to give thereby, leading to abuse of over 50% DOD or a bad setup... These are the reasons why LFP stands out and consider the a better replacement of lead acid how ever, availability and cost is the major challenge at the moment. |
Re: Solar Energy, A Complement To FTA by unicmarket: 7:32am On Feb 04, 2020 |
abbeyforex: Ohh, no problem, if you would, chat me up on my whatsapp no at my signature |
Re: Solar Energy, A Complement To FTA by ojeysky(m): 7:44am On Feb 04, 2020 |
Barezzi: Am open to correction Sir, I assumed 100% DOD for lithium and 50% DOD for Lead Acid....Oya tell me where I misyarn |
Re: Solar Energy, A Complement To FTA by ICraft(m): 8:11am On Feb 04, 2020 |
ojeysky: from my Opinion, there is no battery that is happy with 100%DOD, that's an invitation to short lifespan. I am completely off grid in my office, I use Lithium Ion and my BMS allows maximum voltage per cell 4.1v during charging and lowest discharge level is 3.2v per cell. that range accounts for about 70%DOD. I have had no noticeable capacity loss since I installed the Lithium ion (December 2016). The case would have been different if I do 100%DOD 4 Likes |
Re: Solar Energy, A Complement To FTA by ojeysky(m): 8:22am On Feb 04, 2020 |
ICraft: I agree that putting the lithium consistently at 100% DOD will certainly affect life span in the long run (just as doing 50% lead will as well). However the intention was to give a capacity equivalent else I will actually say the better DOD spot for a lead acid will be 20/30% while that of lithium is good at 70/80%. That way the lead acid may be able to survive up to 75% life span of a lithium. It still won't last the years of a good lithium but should be close. That said, am curious at your lithium voltage figures, do you mean your batteries actually hold voltage at 4.1v? As that seem like a max charge voltage to me (though I don't even get the high in my case). |
Re: Solar Energy, A Complement To FTA by ICraft(m): 9:31am On Feb 04, 2020 |
ojeysky: I believe your Battery is Lithium ion Phosphate (LifePO4). your max voltage per cell is considerably lower, about 3.6v per cell. I use Lithium Ion. Max charge voltage per cell is 4.2v. I set my BMS to shut down Charging once any cell pack reaches that set voltage (4.1v). I don't do float charge |
Re: Solar Energy, A Complement To FTA by simydan(m): 9:32am On Feb 04, 2020 |
ojeysky: He might be using 18650 cells which has a voltage of 3.7V against 3.2V for LFP cells. So, expect his charging voltage to be higher as nominal cell voltage is higher. Correct me if I'm wrong sir! 1 Like |
Re: Solar Energy, A Complement To FTA by oliyeniun: 2:49pm On Feb 04, 2020 |
hello house, i have a solar installation: 24V system, 1200Watts PV array, SuNex 130A MPPT CC (used to have an Epever CC which the installer blew up and replaced with this) 2 200AH Quanta batteries, bought last year and a bluegate 2KVA / 24V inverter. In my location as early as 10am, the battery indicators on each battery is already reading 14.1V because we have plenty sun ![]() the issue is that since i changed from the Prag inverter i was using before to this bluegate inverter, when there is no NEPA and the inverter is on at this time, it goes turns off once the voltage reading on each of the battery gets to 14.1V and except i put plenty load on the inverter to bring the voltage down, it keeps tripping off, which i suspect is due to excess current and the possibility that the battery is full and the solar is still charging the battery (i may be wrong and i stand to be corrected). i also read it somewhere that Quanta manufacturers have a cut off voltage for longevity of their batteries at a much lower voltage (between 13.5-13.6 thereabout). i contacted an installer about the problem and he said i should install a circuit breaker between: i. the Solar Panels and the CC (60A) ii. the CC and the battery (30A) iii. the battery and the inverter (30A) this instruction is a bit strange to me and i am humbly asking the house what they think the problem might be and if the recommendation of the installer should be followed and if not, what should be done. I am counting on the house o. this investment must not waste o. Thank you. |
Re: Solar Energy, A Complement To FTA by SolnergyPower: 4:04pm On Feb 04, 2020 |
I suspect your Solar Charge Controller, it may not be working well. Have you tried disconnecting your Panels as at when the inverter starts tripping OFF? If you haven't, please do and observe the inverter's behaviour. oliyeniun: 1 Like |
Re: Solar Energy, A Complement To FTA by ceaser: 5:04pm On Feb 04, 2020 |
ojeysky: His numbers suggest his own brand is likely 1-8-6-5-0 cells. They max out at 4.2, nominal at 3.2 and Low discharge protection at 2.9. So in this sense, he can still comfortably discharge it further to 3.0v per cell without harming the battery. @Ojesky, yours is LFP and the voltage parameters are quite different from that of his. In his case, 12v nominal is achieved with 3s config while in the case of yours, 12v nominal is achieved with a 4s config. |
Re: Solar Energy, A Complement To FTA by ceaser: 5:06pm On Feb 04, 2020 |
ICraft: Sorry I didn't know that has been responded to. But sha bro ICraft ![]() How have you managed with 18650 for so long? I believe your pack isn't DIY but most likely factory made. |
Re: Solar Energy, A Complement To FTA by ICraft(m): 6:08pm On Feb 04, 2020 |
ceaser: purely DIY, I have a very stringent test process, first test for heaters with thermal camera, we then test for capacity( I have 180 liitokala Lii-500 capacity testers that can test 720 batteries per day. 4 batteries each) then we test for self discharge. out of lets say 10,000 cells, only about 4,0000 may pass. we don't solder cells, we spot weld to avoid corrosion. finally we use 4amp fuse wire to link all the cells to the bus bars. we also use active cell balancers lastly, a well caliberated BMS that you can trust. I dont expect any less than 5 years from my batteries. you are right my office is a factory, and its open to the diy community to come in, test and build packs for a litttle fee and go. all tools you need and more available. powered by 42 pcs 320 watts solar panels and 80KWH of 18650cells. 10 Likes 3 Shares
|
Re: Solar Energy, A Complement To FTA by idsolar(m): 8:29pm On Feb 04, 2020 |
oliyeniun: I am suspecting that the inverter battery over-voltage cut off set point is likely on 28vdc. if I am in your shoes I will change the CC maximum battery charge cut-off set from 14.1 to 14 or 13.9v to check 2 Likes |
Re: Solar Energy, A Complement To FTA by adrusa: 8:29pm On Feb 04, 2020 |
ICraft: So can you build a pack for me 200AH 48V? |
Re: Solar Energy, A Complement To FTA by ICraft(m): 9:23pm On Feb 04, 2020 |
adrusa: If you have the time, it's more affordable for you to buy cells and do your packs yourself, but if you don't have the time reach me on phone. we can easily do that for you. my contact is a bove 1 Like |
Re: Solar Energy, A Complement To FTA by ojeysky(m): 9:25pm On Feb 04, 2020 |
ICraft: Thanks for the clarification. I heard those lithium ion are quite dangerous for newbies if charging and connections is not handled properly but I can see that you are Pro DIY user wey pass my level. Make people like us dey manage LFP jeje ![]() 1 Like |
Re: Solar Energy, A Complement To FTA by justcallmenuel(m): 9:42pm On Feb 04, 2020 |
60amphs Fangpusun charge controller available, #120000. Contact us on 08168986461
|
(1) (2) (3) ... (664) (665) (666) (667) (668) (669) (670) ... (1909) (Reply)
Free To Air Satellite Tv General Thread
Viewing this topic: 1 guest(s)
(Go Up)
Sections: politics (1) business autos (1) jobs (1) career education (1) romance computers phones travel sports fashion health religion celebs tv-movies music-radio literature webmasters programming techmarket Links: (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Nairaland - Copyright © 2005 - 2025 Oluwaseun Osewa. All rights reserved. See How To Advertise. 90 |