Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 2:41pm On Sep 13 |
When I want to on the fridge I off everything. It doesn't pick the fridge, it only picks the light inside the fridge if I open the fridge door. olopan: |
Re: Solar Energy, A Complement To FTA by Iinnov8: 2:42pm On Sep 13 |
preyeamaorutobi: I see. Well, I doubt your fridge uses an inverter compressor like you said, else the inverter would have powered it. I suspect it is a normal compressor that has the usual high starting surge. You can confirm so by putting on the fridge while your gen is on. If it "draws" the gen on start up, then it is the normal compressor. If you confirm it to be a normal compressor, then it may be that your inverter is not truly 1.5kva so it is not able to accommodate that starting surge which could be over 1000w. We are also not sure whether your battery is getting enough charge particular from the solar panels, likely because the solar panels are not original (sorry to say so, I am sure you have read about labelling of panels here), so it could also be the case that the battery is not getting sufficient charge to supply the inverter the juice it needs to cushion the start up surge of the fridge between it trips off or so. Begin by leaving the battery to itself to charge full either through grid or via solar for a day. Then put off your ALL your load, and switch on ONLY the fridge first. If it doesn't power the fridge, then the inverter is likely the problem and a low hanging fruit you can resolve first. Update us on this and we can discuss further. 2 Likes |
Re: Solar Energy, A Complement To FTA by Iinnov8: 2:44pm On Sep 13 |
isangjohnson: I agree. Very wrong advise from a place of ignorance. My first set up was a 12v connection with just one battery and it powered by 200+ litre fridge of 110w or so. |
Re: Solar Energy, A Complement To FTA by Iinnov8: 2:48pm On Sep 13 |
preyeamaorutobi: Usually, if a fridge is switched off and then put on within a short while, the internal light will come on, but the compressor will take some minutes to pick up. |
Re: Solar Energy, A Complement To FTA by Obnoxious2001(m): 2:57pm On Sep 13 |
preyeamaorutobi: Your inverter is 1.5kva which Is adequate to provided power for the fridge. You just need more current (battery) so you don't damage your existing battery ( i no wan dey explain in details) Your 60A mppt controller would not function to its maximum abilities since your system is a low voltage system so pwm are better 2 Likes |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:02pm On Sep 13 |
I think it's an inverter fridge because when the gen is on it doesn't shake it at all. Rating 220-240v - 50/60Hz Rated current 1.15A Defrosting input 220v/230 - 240v Rated input of heater cord - 95w Annual energy consumption - 235kwh/year Rated power input - 65w Dimensions - 555(W) x 585(D) x 1520 (H) mm Iinnov8: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:08pm On Sep 13 |
I'm having issues posting image olopan: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:12pm On Sep 13 |
Thank you for this. That was why I came to this forum. So please what will you advice considering my issue. This is the fridge specs, it's an inverter Rating 220-240v - 50/60Hz Rated current 1.15A Defrosting input 220v/230 - 240v Rated input of heater cord - 95w Annual energy consumption - 235kwh/year Rated power input - 65w Dimensions - 555(W) x 585(D) x 1520 (H) mm isangjohnson: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:13pm On Sep 13 |
Please can I know the difference between 1.5kva 12v and 2.5kva 24V isangjohnson: |
Re: Solar Energy, A Complement To FTA by Iinnov8: 3:20pm On Sep 13 |
preyeamaorutobi: Share pics, make and model of the fridge so that we can look it up. But also try the other recommendation I offered |
Re: Solar Energy, A Complement To FTA by KingGeedorah(m): 3:22pm On Sep 13 |
Good day House, I recently bought a solar generator (Ecoflow Delta 2) . I would like advice on how to connect it to the house to that it can power up my house lights and 2 sockets for fridge and Tv. Presently l use extension cables to power my fridge and entertainment centre. See attachment from their website. Thank you in advance
|
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:29pm On Sep 13 |
The battery usually charge to the fullest and float. Maybe I'll on the fridge again and keep it for about 20 minutes to see if it will pick. What do you mean by a low hanging fruit? Iinnov8: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:32pm On Sep 13 |
What was the inverter kva? And was the fridge an inverter fridge? Iinnov8: |
Re: Solar Energy, A Complement To FTA by Valto(m): 3:39pm On Sep 13 |
SEPTEMBER PRICE SLASH CONTINUES... Brand new REPT 280AH Lifepo4 Lithium battery cells available at discounted price 115k each. further discounts on large quantity whatsapp 08020574628 or telegram@ValtechEnergy
|
Re: Solar Energy, A Complement To FTA by Iinnov8: 3:40pm On Sep 13 |
preyeamaorutobi: How do you know the battery gets full and floats regularly? Do you confirm so with an external voltmeter/multimeter? If you are relying on the reading from the inverter, then you are on a long thing as the voltage reading from the inverter is probably incorrect. Low hanging fruit is not a technical terminology. It simply means an option that is easy to accomplish first before moving on to harder option. 1 Like |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:49pm On Sep 13 |
Okay, I'll on it for a while and see if it picks. Iinnov8: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:52pm On Sep 13 |
Thank you sir Obnoxious2001: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 3:54pm On Sep 13 |
Okay thank you. It's an LG fridge/freezer. I can't send picture Iinnov8: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 4:02pm On Sep 13 |
I know from the mppt charge controller. Thank you so much Iinnov8: |
Re: Solar Energy, A Complement To FTA by Iinnov8: 4:05pm On Sep 13 |
preyeamaorutobi: First picture is the fridge. It is a Haier Thermocool 259L non-inverter deep freezer. Second picture is the inverter. It is an Easun pure sine-wave offgrid inverter rated in watts, just like your appliances. It is rated 3000w/1500w (peak/continuous). You can see test videos of the inverter through this thread: https://www.nairaland.com/7833852/3000w-easun-pure-sine-wave 2 Likes
|
Re: Solar Energy, A Complement To FTA by olopan(m): 4:07pm On Sep 13 |
Check my profile send your pictures to the account on whatsAPP, I'd help you post it here. i still have the feeling of something is not done right preyeamaorutobi: 1 Like |
Re: Solar Energy, A Complement To FTA by olopan(m): 4:11pm On Sep 13 |
OgakingGozilla rival Get an original 13A plug decommision your old generator cable if you have it rewire the generator cable and switch the generator change over to the generator side. you should have power. if confused about this or running into a more complex situation, then you need a trained professsional. KingGeedorah: 1 Like |
Re: Solar Energy, A Complement To FTA by BRIGHTSOLAR(m): 4:16pm On Sep 13 |
Instalment payment Payment duration 5 years ✳️₦130,000 per month for first year ✳️₦146,000 per month for second year ✳️₦164,000 per month for third year ✳️₦185,000 per month for fourth year ✳️₦208,000 per month for fifth year 🌟After 5 years it becomes yours 🌟Zero down payment Upload all required KYC documents Download the contract agreement and upload the signed contract Make payment for first month ₦130,000 The solar system will be installed If the client is buying outright purchase ₦7,300,000 If client want zero deposit instalment payment for 5 years ownership. ₦9,999,000 Whatsapp:07032352337
|
Re: Solar Energy, A Complement To FTA by KingGeedorah(m): 4:19pm On Sep 13 |
Thanks for the feedback Can l have a situation where l keep the old generator cable but run a cable just for the solar inverter, where the solar inverter only powers lights and selected sockets. olopan: |
Re: Solar Energy, A Complement To FTA by HeavenlyBang(m): 4:32pm On Sep 13 |
BRIGHTSOLAR: This is...horribly expensive. 7 Likes |
Re: Solar Energy, A Complement To FTA by olopan(m): 4:44pm On Sep 13 |
you need an electrician for this part, it is not something an untrained person can venture into. KingGeedorah: 1 Like |
Re: Solar Energy, A Complement To FTA by Obnoxious2001(m): 4:46pm On Sep 13 |
KingGeedorah:You need an electrician at this point. 1 Like |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 5:03pm On Sep 13 |
Wow nice. How can I get it.? Iinnov8: |
Re: Solar Energy, A Complement To FTA by preyeamaorutobi(m): 5:18pm On Sep 13 |
Please what's the best solar system for these appliances?. 1. 7.5kg Washing Machine 2. Inverter Fridge double door Rating 220-240v - 50/60Hz Rated current 1.15A Defrosting input 220v/230 - 240v Rated input of heater cord - 95w Annual energy consumption - 235kwh/year Rated power input - 65w Dimensions - 555(W) x 585(D) x 1520 (H) mm 3. 120W 50inches Tv 4. Bulbs 5. Few phones and a Power Bank 6. Ceiling Fan 90W 7. Chargeable fan 45W 8. 1-2 Laptop These appliances are not to be used at the same time. When TV is on, fridge will be off and vice versa. Please I need the best economical solar system package for these appliances. |
Re: Solar Energy, A Complement To FTA by Iinnov8: 5:23pm On Sep 13 |
preyeamaorutobi: My contact is in my signature. Chat me up let's discuss. 1 Like |
Re: Solar Energy, A Complement To FTA by jasp12(m): 6:13pm On Sep 13 |
@ Dam5reey1 @dollarnaira @ Obnoxious2001 What could be the reason PV input is zero on my Felicity 3kva inverter (pv reading 37V testing using multimeter)
|
Re: Solar Energy, A Complement To FTA by Obnoxious2001(m): 7:03pm On Sep 13 |
jasp12:Check if you have met the minimum required PV input voltage 2 Likes |
(1) (2) (3) ... (1802) (1803) (1804) (1805) (1806) (1807) (1808) ... (1827) (Reply)
FTA Live Football Matches Announcement Thread / Free To Air Satellite Tv General Thread
(Go Up)
Sections: politics (1) business autos (1) jobs (1) career education (1) romance computers phones travel sports fashion health religion celebs tv-movies music-radio literature webmasters programming techmarket Links: (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Nairaland - Copyright © 2005 - 2024 Oluwaseun Osewa. All rights reserved. See How To Advertise. 79 |